£4,650.00
When building medium- and large-scale PV farms, designers, guided by the need to ensure the highest possible energy yield and thus the maximum return on investment, select inverters with a voltage of 1500 V DC / 800 V AC. Testing of such a system must address both the AC and DC sides of the PV system. Testing of all AC circuits must be performed in accordance with the requirements of IEC 60364-6.
The output voltage of 800 V AC, which in real conditions often exceeds this value, poses a huge problem for contractors and servicing companies, since for such high voltages there are no devices on the market to check the installation for compliance with the conditions of electric shock protection in terms of measuring the impedance of the short circuit loop.
Sonel was the first company in the world to take on the challenge of creating a fault loop impedance meter for operating voltages up to 900 V AC and measurement category CAT IV 1000 V. This is how the Sonel MZC-340-PV meter was created.
The energy released at mains voltage of 800-900 V AC can pose a danger to the personnel performing measurements. That’s why the Sonel MZC-340-PV is only wirelessly controlled.
The instrument is used for measurements in networks with rated voltage up to 900 V AC, where the prospective fault current may reach over 100 kA, as measured according to EN 61557.
These parameters make the meters perfect for tests and measurements at wind farms, high-speed rail and in facilities controlled by power companies.
For more information visit the Power Quality Expert Page
Is the Sonel MZC-340-PV too much for what you need? Then check out the Sonel MZC-330S with the video below:
Choose the Sonel MZC-340-PV high-current short-circuit loop impedance meter for operating voltages up to 900 V AC with measurement category CAT IV 1000 V and efficient ventilation system for smooth and effective operation without downtime. It is only wirelessly controlled.
In case of multiple short-circuit loop impedance measurements, some measuring devices may get blocked. This problem does not affect the Sonel MZC-340-PV meter. To prevent blockages, the device is equipped with a special high performance ventilation system that significantly reduces the time required to cool the short-circuit resistor. The Sonel MZC-340-PV advanced high current meter is the right choice for professionals in the power, electrical, as well as installation and measurement industries. The device combines extensive measuring capabilities with high durability and resistance to harsh working conditions. A specially developed ventilation system translates into greater efficiency and significantly reduces working time.
Measurement functions | Measurement range | Display range | Resolution | Accuracy |
---|---|---|---|---|
Voltage | 0 V…900 V | 0 V…900 V | 1 V | from ±(2% m.v. + 2 digits) |
Frequency | 45.0 Hz…65.0 Hz | 45.0 Hz…65.0 Hz | 0.1 Hz | ±(0.1% m.v. + 1 digit) |
Short-circuit loop parameters | Â | Â | Â | Â |
4p method – high current measurement maximum current 300 A | 7.2 m?…1999 m? acc. to EN 61557-3 | 0.0 m?…1999 m? | from 0.1 m? | ±(2% m.v. + 2 m?) |
Short-circuit current readings | Â | Â | Â | Â |
4p method – high current measurement network voltage 115 V…690 V | up to 400 A…111.1 kA acc. to EN 61557-3 | 110.0 A…199.9 kA | from 0.1 A | Calculated on the basis of error for fault loop |
Touch and shock voltage | Â | Â | Â | Â |
4p method – high current measurement | 0 V…100 V | 0 V…100 V | 1 V | ±(10% m.v. + 2 digits) |
Download: Sonel MZC-340-PVÂ [HERE]
Order now from our brand new energy division!
Di-LOG Energy